D2 Formula and Conversion Guide
The formulas and conversion values you need for California water distribution operator math, in plain English. Free to read. No account needed.
Values were checked against the State Water Board Exam Conversion Sheet revised 4/30/2026. Always confirm values with the official exam conversion sheet you get on exam day.
How to use this guide
- Read the question and decide what it is asking for: an area, a volume, a pressure, a flow, or a dose.
- Pick the formula that matches. The formula tables below say when to use each one.
- Check your units. Change feet to inches, gallons to millions of gallons, and so on, before you multiply.
- Do the math with all your digits and round only at the end.
Conversion values
Volume
- 1 cubic foot = 7.48 gallons
- 1 cubic yard = 27 cubic feet
- 1 MG = 1,000,000 gallons
- 1 CCF = 100 cubic feet = 748 gallons
- 1 acre-foot = 325,851 gallons
- 1 gallon = 3.79 liters
- 1 liter = 1,000 mL
Weight
- 1 gallon of water = 8.34 pounds
- 1 cubic foot of water = 62.3832 pounds
- 1 pound = 454 grams = 7,000 grains
- 1 pound = 0.454 kg
- 1 liter of water = 1,000 grams
- 1 ton = 2,000 pounds
Pressure
- 1 psi = 2.31 feet of head
- 1 foot of head = 0.433 psi
Flow
- 1 MGD = 1,000,000 gallons per day
- 1 MGD = 694.4 gpm
- 1 MGD = 1.55 cfs
- 1 cfs = 448.8 gpm
Concentration
- 1% = 10,000 mg/L
- 1 mg/L = 1 ppm
- 1 grain per gallon = 17.1 mg/L
- 1 gram per liter (g/L) = 1,000 mg/L
Length
- 1 foot = 12 inches
- 1 mile = 5,280 feet
- 1 yard = 3 feet
- 1 foot = 0.305 meters
Time
- 1 day = 24 hours = 1,440 minutes = 86,400 seconds
- 1 hour = 60 minutes
- 1 minute = 60 seconds
Circles
- Area of a circle = 0.785 × D × D (D in feet)
- Circumference = 3.14 × D
- Use 3.14 for pi
Area
- 1 acre = 43,560 square feet
Power
- 1 horsepower = 33,000 foot-pounds per minute
- 1 horsepower = 746 watts = 0.746 kW
Formulas
Area
Use these to find the size of a flat surface, like the floor of a tank or the end of a pipe.
- Rectangle = Length × Width
- Circle = 0.785 × D × D (D in feet)
Volume
Use these to find how much a tank or pipe holds. Then change cubic feet to gallons if you need to.
- Rectangular tank = L × W × D
- Cylinder or pipe = 0.785 × D × D × Height (or Length)
- Gallons = Cubic feet × 7.48
Pressure
Use these to switch between feet of head and psi. Water pressure comes from the height of the water.
- psi = Feet of head × 0.433
- Feet of head = psi × 2.31
Flow and velocity
Use these when the question talks about how fast water moves or how long it takes to fill.
- Q = A × V (Q in cfs, A in sq ft, V in ft/sec)
- V = Q ÷ A
- Time to fill or drain = Volume ÷ Flow
Detention time
Use this to find how long water stays in a tank or pipe. Make sure volume and flow use matching units.
- Detention time = Volume ÷ Flow (matching units)
Pounds formula
Use this to turn a dose in mg/L into pounds of chemical. It is one of the most common formulas on the exam.
- lbs/day = Flow (MGD) × Dose (mg/L) × 8.34
- lbs = Volume (MG) × Dose (mg/L) × 8.34
Chemical purity
Use these when a chemical is not 100% pure, or when it comes as a liquid.
- lbs of product = lbs of pure chemical ÷ Purity (as a decimal)
- Weight of 1 gallon of solution = 8.34 × Specific gravity
- Chemical weight (lbs/gal) = Specific gravity × 8.34
- Specific gravity = Chemical weight (lbs/gal) ÷ 8.34
- Gallons of liquid chemical = lbs needed ÷ (Strength as a decimal × Chemical weight in lbs/gal)
Chlorine
Use this to find how much chlorine to add to get the residual you want.
- Dose = Demand + Residual
Interior surface area
Use these to find the surface area inside a tank, such as the walls and floor that need cleaning or coating.
- Cylinder walls = 3.14 × D × H
- Cylinder floor (or roof) = 0.785 × D × D
- Rectangle walls = 2(L × H) + 2(W × H)
- Rectangle floor (or roof) = L × W
Chloramination
Use these to find how much ammonia goes with a given amount of chlorine.
- Ratio = lbs of chlorine ÷ lbs of ammonia-nitrogen (by weight)
- lbs of NH3-N = lbs of chlorine ÷ Ratio
Feed pumps
Use this to change a pump setting in mL/min to gallons per day.
- gal/day = mL/min × 1,440 ÷ (1,000 mL/L × 3.785 L/gal)
Dilution
Use this to find how much strong solution to mix with water to get a weaker one.
- C1 × V1 = C2 × V2
Force
Use these to find the force that pressure puts on a flat surface, such as a valve face.
- Pounds of force = psi × Area (square inches)
- Area of a valve face (sq in) = 0.785 × D × D (D in inches)
Thrust blocks
Use this to size a concrete block that holds a pipe bend in place.
- Bearing area (sq ft) = Thrust (lbs) ÷ Soil bearing capacity (lbs/sq ft)
Wells
Use these for well water levels and airline readings.
- Drawdown = Pumping water level − Static water level
- Feet of water above the airline = psi × 2.31
Demand
Use this to find how much water each person uses in a day.
- Gallons per capita per day = Gallons per day ÷ Population
SCADA (4 to 20 mA)
Use these to change between a 4 to 20 mA signal and the real reading it stands for.
- Process value = ((Live signal mA − 4) ÷ 16) × Process range
- Signal mA = (Process value ÷ Process range) × 16 + 4
Maps
Use this to turn a distance on a map into a real distance.
- Actual distance = Map distance × Scale
Pumping
Use these to find the power a pump needs, and what it costs to run. Efficiency is always a decimal in the formula.
- Water HP = (gpm × Head in feet) ÷ 3,960
- Brake HP = Water HP ÷ (Pump % efficiency ÷ 100)
- Motor HP = Brake HP ÷ (Motor % efficiency ÷ 100)
- Cost ($) = HP × 0.746 × Operating hours × $/kWh
Flow from a horizontal pipe
- Fall time (sec) = √(2 × Height in feet ÷ g), with g = 32.2 ft/s² (not on the sheet, so the question states it)
- Speed (ft/sec) = Distance the stream lands out from the pipe (ft) ÷ Fall time
- Q = A × V, then gpm = cfs × 448.8
Meter accuracy
Use this to compare what a meter reads with the water that really went through it.
- Accuracy (%) = (Meter reading ÷ Actual volume) × 100
Tank level
Use these when a tank is described by the gallons in each foot of depth.
- Gallons per foot of depth = 0.785 × D × D × 7.48
- Gallons = Gallons per foot × Depth (ft)
Averages
Use these for by-product results. A running annual average is the average of the last four quarters.
- Average = Sum of results ÷ Number of results
- Running annual average = Average of the last four quarterly averages
Percents
Use these for easy points: percent and decimal changes, and the area of a triangle.
- Decimal = Percent ÷ 100
- Percent = Decimal × 100
- Area of a triangle = ½ × Base × Height
How answers are rounded
Keep every digit while you work, then round only the final answer.
| Size of answer | Round to |
|---|---|
| 100 or more | A whole number |
| 10 to 99.99 | 1 decimal place |
| 1 to 9.99 | 2 decimal places |
| Less than 1 | 3 significant figures |
Worked examples
Here are step-by-step solutions to a few sample problems.
Example 1: Unit Conversions
A water system delivers 6.5 MGD. What is this flow in gallons per minute (gpm)?
- Use 1 MGD = 694.4 gpm. To go from MGD to gpm, multiply.6.5 MGD × 694.4 gpm/MGD = 4,513.6 gpm
- Round only at the very end. The steps above kept every digit, even though they show shorter numbers.4,513.6 rounds to 4,514 gpm
Formula used: gpm = MGD × 694.4
Answer: 4,514 gpm
Example 2: Area and Volume
A cylindrical storage tank is 80 feet in diameter. The water level is 26 feet. How many gallons of water are in the tank?
- Find the area of the circle (tank floor). Area = 0.785 × D × D.0.785 × 80 ft × 80 ft = 5,024 sq ft
- Find the volume in cubic feet. Multiply the area by the water depth.5,024 sq ft × 26 ft = 130,624 cu ft
- Change cubic feet to gallons. Multiply by 7.48.130,624 cu ft × 7.48 gal/cu ft = 977,068 gal
- Round only at the very end. The steps above kept every digit, even though they show shorter numbers.977,067.52 rounds to 977,068 gallons
Formula used: Gallons = 0.785 × D × D × H × 7.48
Answer: 977,068 gallons
Example 3: Pressure and Head
The water surface in a tank is 12 feet above a pressure gauge. With no water flowing, what will the gauge read, in psi?
- Use 1 foot of head = 0.433 psi. Multiply.12 ft × 0.433 psi/ft = 5.196 psi
- Round only at the very end. The steps above kept every digit, even though they show shorter numbers.5.196 rounds to 5.2 psi
Formula used: psi = Feet of head × 0.433
Answer: 5.2 psi
Independent study tool. Not affiliated with or endorsed by the California State Water Resources Control Board. Always confirm values with the official exam conversion sheet.